17-5174-1.00, 17-5164-9..0
PTB 11 ATEX 2009 X
IECEx PTB 11.0051 X
PROFIBUS Z01762 (PROFIBUS)
PROFIBUS Z10667 (PROFINET IO)
DNV A-13339
TC RU C-DE.BH02.B.00005
KCS KTL 13-KB4BO-0310
KCS KTL 13-KB4BO-0311
KCS KTL 13-KB4BO-0312
UL BR 13.0241X
II 2G Ex d e [ib] IIC T4 Gb
Ex d e [ib] IIC T4 Gb
Class I, Zone 1
-20 °C up to +60 °C
The Rail Control Unit (RCU) ANTARES is the central unit in the ANTARES system. It consists of the head module and the connection module. Various field bus and Ethernet-based head modules are available. There is no need to use an isolating repeater to connect them. Redundancy is achieved with no single point of failure by connecting two PROFIBUS-DP RCUs. The head module, consisting of the CPU, the communication interface and an integrated power supply unit, is produced with the Ex d type of protection and is plugged into the corresponding connection module. The innovative interlocking technology ensures a reliable connection. The hot swap capability allows the head module to be replaced even in an explosive atmosphere. The connection module has an integrated Ex e junction box. A version is also available for armoured leads. The system is configured by means of Software ANTARES Designer using the USB interface. See the system description for installation instructions.
Protection class | (EN 60529) RCU: IP 54 Internal system bus: IP 30 (in the ANTARES system construction) |
Dimensions | RCU: (B x H x T) 114 mm x 192 mm x 298 mm |
Material | Enclosure material Connection module: PA Head module: aluminium die-casting, PA |
Installation | Mounting rail TH 35-15 DIN EN/IEC 60715 (steel, galvanized steel) flush on mounting plate |
Storage temperature | -25 °C up to +70 °C |
Humidity | 5 up to 95 %, non-condensing |
Vibration | (EN/IEC 60068-2-6) 2 g/7 mm; 5 Hz up to 200 Hz into all 3 axes |
Shock resistance | (EN/IEC 60068-2-27) 15 g/11 ms, ± 3 shocks per direction |
Weight | approx.5 kg |
Display | LED connection modules: Operation: LED RUN Communication: LED COM Redundancy (primary): LED PRI Error: LED ERR |
Interface | Configuration Interface: USB |
Memory | Back up: SD card |
Voltage | DC 24 V -15 %, + 25 % Overvoltage category: II |
Power | max. 100 W |
Bus interface | Process connection: Internal Bus communication – 10 + 2 pole connector PROFIBUS-DP – Full redundancy possible up to 1.5 Mbit/s Ethernet 100BaseT with integrated switch – PROFINET – MODBUS/TCP – EtherNet/IP |
*Refer to the documentation for more detailed information
Weight | 5.0 kg |
---|---|
Dimensions | 14.1 × 19.2 × 29.8 cm |