The ComExflexpotentiometer is used in almost all hazardous (potentially explosive) areas where machine functions are controlled by means of adjustable voltage distributors.The module can be combined with a potentiometer actuator (scale graduation 0 to 10). A junction box is available as a safe and convenient means of installing the potentiometer in a control panel.The conductors are connected by means of terminals on the back of the module which have an increased safety level. The easy installation of the potentiometer actuating element without the need for tools,ensures conformance to the high IP degree of protection.Note for installation and revision workFor rated voltage:- ≤ AC 50 V/≤ DC 120 V (Safety extra low voltage in conformance to DIN VDE 0100 T. 410), The potentiometer drive shaft can be operated without an actuator.- ≥ AC 50 V to max. AC/DC 230 V, Potentiometer drive shaft must be operated with an actuator or disconnected from voltage.
| Protection class | determined by the actuating element and control station enclosure, min. IP 66, terminals IP 20 (IEC 60529) | 
|---|---|
| Dimensions | see data sheet | 
| Material | Enclosure material: Thermoplastic Resistance material: Carbon layer on ceramics | 
| Mechanical life | 25000 sinusoidal cycles | 
| Storage temperature | -55 °C to +70 °C | 
| Weight | approx. 110 g | 
| Voltage | Rated insulation voltage: 500 V Max. rated: operating voltage AC/DC 230 V | 
| Power | max. 1 W for Ta ≤ +40 °C | 
| Resistance | Resistance levels: 1 kOhm to 10 kOhm Curve shape: linear Resistance tolerance: + 20 % | 
| Connection | double terminals 2 x 2.5 mm², fine-stranded |